Wire Chart
Ampacities of Insulated Conductors (From NEC Table 310-16)
Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried) (Based on Ambient Temperature of 30° C, 86° F) | ||||||
Size | Copper Conductors | Aluminum Conductors Copper-Clad Conductors | ||||
60° C (140° F) | 75° C (167° F) | 90° C (194° F) | 60° C (140° F) | 75° C (167° F) | 90° C (194° F) | |
AWG Kcil | Types | Types | Types | Types | Types | Types |
TW UF | RHW THW THWN XHHW USE ZW | TBS SA SIS FEP FEPB RHH THHN THWN XHHW | TW UF | RHW THHW THW THWN XHHW USE | TBS SA, SIS THHN, THHW THW-2 THWN-2 RHH, RHW-2 USE-2 XHH, XHHW XHHW-2, ZW-2 | |
18 | - | - | 14 | - | - | - |
16 | - | - | 18 | - | - | - |
14 1 | 20 | 20 | 25 | - | - | - |
12 1 | 25 | 25 | 30 | 20 1 | 20 1 | 25 1 |
10 1 | 30 | 35 | 40 | 25 | 30 1 | 35 1 |
8 | 40 | 50 | 55 | 30 | 40 | 45 |
6 | 55 | 65 | 75 | 40 | 50 | 60 |
4 | 70 | 85 | 95 | 55 | 65 | 75 |
3 | 85 | 100 | 110 | 65 | 75 | 85 |
2 | 95 | 115 | 130 | 75 | 90 | 100 |
1 | 110 | 130 | 150 | 85 | 100 | 115 |
1/0 | 125 | 150 | 170 | 100 | 120 | 135 |
2/0 | 145 | 175 | 195 | 115 | 135 | 150 |
3/0 | 165 | 200 | 225 | 130 | 155 | 175 |
4/0 | 195 | 230 | 260 | 150 | 180 | 205 |
250 | 215 | 255 | 290 | 170 | 205 | 230 |
300 | 240 | 285 | 320 | 190 | 230 | 255 |
350 | 260 | 310 | 350 | 210 | 250 | 280 |
400 | 280 | 335 | 380 | 225 | 270 | 305 |
500 | 320 | 380 | 430 | 260 | 310 | 350 |
600 | 355 | 420 | 475 | 285 | 340 | 385 |
700 | 385 | 460 | 520 | 310 | 375 | 420 |
750 | 400 | 475 | 535 | 320 | 385 | 435 |
800 | 410 | 490 | 555 | 330 | 395 | 450 |
900 | 435 | 520 | 585 | 355 | 425 | 480 |
1000 | 455 | 545 | 615 | 375 | 445 | 500 |
1250 | 495 | 590 | 665 | 405 | 485 | 545 |
1500 | 520 | 625 | 705 | 435 | 520 | 585 |
1750 | 545 | 650 | 735 | 455 | 545 | 615 |
2000 | 560 | 665 | 750 | 470 | 560 | 630 |
Correction Factors for Ambient Temperature Over 30° C, 86° F
| ||||||
Ambient Temperature |
For Ambient Temperatures Over 30° C, 86° F, multiply the ampacities shown above by the appropriate factor show below:
| |||||
21-25 C, 70-77 F | 1.08 | 1.05 | 1.04 | 1.08 | 1.05 | 1.04 |
26-30 C, 78-86 F | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
31-35 C, 87-95 F | .91 | .94 | .96 | .91 | .94 | .96 |
36-40 C, 96-104 F | .82 | .88 | .91 | .82 | .88 | .91 |
41-45 C, 105-113 F | .71 | .82 | .87 | .71 | .82 | .87 |
46-50 C, 114-122 F | .58 | .75 | .82 | .58 | .75 | .82 |
51-55 C, 123-131 F | .41 | .67 | .76 | .41 | .67 | .76 |
56-60 C, 132-140 F | - | .58 | .71 | - | .58 | .71 |
61-70 C, 141-158 F | - | .33 | .58 | - | .33 | .58 |
71-80 C, 159-176 F | - | - | .41 | - | - | .41 |
1 The load current rating and the overcurrent protection for conductor types shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10 AWG aluminum and copper-clad aluminum after any correction factors for ambient temperature and number of conductors have been applied.
|